Drive-Temp Fan Control on a Supermicro H12 with a Passed-Through HBA

My drives were running in the mid-40s. Not dangerous, but warmer than I wanted, and the only way to cool them was to set the BMC fan mode to Full — which on a Supermicro 826 means all three mid-wall fans at 7400 RPM, permanently, in a room I sit in.

The fix is a script that reads drive temperatures and sets the BMC’s fan duty cycle directly. That part is well-trodden. What made my setup awkward is that the HBA is passed through to a VM, so the host that can talk to the BMC can’t see the drives, and the guest that can see the drives can’t talk to the BMC. There’s also a second 826 attached as a JBOD, whose drives must not be allowed to influence fans that can’t cool them.

And, spoiler… the real cause of my heat problem turned out to be a fan that wasn’t seated properly after I’d cleaned the case out a few days ago. I’ll come back to that, because it’s the most useful part of this post.

The hardware

  • Supermicro H12SSL-i, EPYC 7502, 512GB RAM, in an SC826 chassis
  • Three populated mid-wall fans (FAN2, FAN3, FAN4); FAN1, FAN5, FANA, FANB empty
  • LSI HBA passed through to a Ubuntu 24.04 VM running MergerFS + SnapRAID
  • Second SC826 as a JBOD on a separate HBA
  • 15 spinners total: 8 in the main chassis, 7 in the JBOD

The host is Proxmox. My Fileserver VM has all the drives passed through to it.

Why the BMC’s own modes don’t solve this

Supermicro boards have four fan modes: Standard, Full, Optimal, and Heavy IO. Read the names carefully, because “Full” doesn’t mean what you’d think. It means manual. In Full mode the BMC stops managing fans and honors whatever duty cycle you write to it. That’s the mode you want.

The problem with the automatic modes is what they’re measuring. Optimal and Standard drive the peripheral fan zone from CPU and system temperatures. Your drives aren’t in that loop at all. On my box, Optimal held the CPU comfortably while the drives climbed into the mid-40s, because from the BMC’s point of view nothing was wrong.

Check your current mode:

1
ipmitool raw 0x30 0x45 0x00

Returns 00 for Standard, 01 for Full, 02 for Optimal, 04 for Heavy IO.

And the current duty cycle per zone:

1
2
ipmitool raw 0x30 0x70 0x66 0x00 0x00
ipmitool raw 0x30 0x70 0x66 0x00 0x01

Zone 0 is typically FAN1–FAN4, zone 1 is FANA/FANB. On my board only zone 0 is populated, so there’s exactly one knob. Confirm which zone your drive-cage fans are on before you script anything — the SC826 backplane and fan wiring vary by chassis revision.

To set a zone manually:

1
2
ipmitool raw 0x30 0x45 0x01 0x01              # Full (manual) mode
ipmitool raw 0x30 0x70 0x66 0x01 0x00 0x32    # zone 0 -> 0x32 (50%)

Full mode is a prerequisite. In Standard or Optimal the BMC accepts your duty writes and then silently overrides them within seconds, which is a confusing way to spend twenty minutes.

Find your floor before you write a curve

Don’t guess at a minimum duty cycle. The BMC clamps below some threshold, and the point where it stops tracking your input is a property of your board and fans, not something you can look up.

Sweep it:

1
2
3
4
5
6
7
8
for d in 0x20 0x28 0x30 0x38 0x40; do
  ipmitool raw 0x30 0x70 0x66 0x01 0x00 $d
  sleep 45
  echo -n "duty $d: "
  ipmitool sensor list 2>/dev/null | awk '/^FAN[234]/{printf "%s ", $3}'
  echo
done
ipmitool raw 0x30 0x70 0x66 0x01 0x00 0x64

My first sweep came back cleanly linear at roughly 105 RPM per percent, with no sign of a floor — so I went lower:

1
2
3
duty 0x0f: 2240 2380 2520
duty 0x14: 2660 2660 2660
duty 0x1a: 2940 2940 2940

Two tells that I’d hit the clamp. The curve flattened: 0x14 to 0x1a moved 280 RPM where the linear region moved about 600 for the same span. And at 0x14 and 0x1a all three fans reported identical RPM, where every other data point had 100–300 RPM of spread between physically different fans. Identical readings across three units means you’re seeing a clamped value, not a measured one.

I took 0x14 (~2660 RPM) as the floor. 0x0f buys almost no real airflow and puts you in the region where behavior stops being predictable.

While you’re here, check your fan sensor thresholds:

1
ipmitool sensor list | grep -i fan

Mine read lower-non-recoverable at 280 RPM and lower-critical at 420. If a fan drops below the non-recoverable threshold the BMC declares a fault and pins every fan at 100% until you reset it. With a floor at 2660 RPM I had enormous headroom, but if yours is tighter, lower the thresholds first:

1
ipmitool sensor thresh FANA lower 100 200 300

The Division of access: the host owns the BMC, guest owns the drives

ipmitool needs to run on the Proxmox host — that’s where the direct access to the BMC is. smartctl needs to run in the VM, because that’s where the passed-through HBA lives. You need a bridge, and the direction matters.

I have the host pull from the guest, not the guest push to the host. If the VM is suspended, crashed, or mid-reboot, the host notices immediately — the SSH call fails and the script responds by going to 100%. If you inverted it, a dead VM would simply stop sending updates and the fans would hold at whatever they were last set to, indefinitely. Loud is the correct failure state; silent is not.

Generate a dedicated key on the host:

1
2
ssh-keygen -t ed25519 -f /root/.ssh/id_fanctl -N '' -C fanctl
ssh-copy-id -i /root/.ssh/id_fanctl.pub root@192.168.172.10

Then, in the VM’s /root/.ssh/authorized_keys, prefix that key with a forced command so it can’t be used for anything else. All on one line:

1
command="/root/scripts/disktemps",restrict ssh-ed25519 AAAAC3Nza... fanctl

restrict disables port forwarding, agent forwarding, X11, and PTY allocation. The forced command means the remote command is ignored entirely — whatever you ask for, disktemps runs.

That last detail is worth knowing when you test it. ssh -i key root@vm true will return successfully whether or not the restriction is in place, because true prints nothing either way. Test with something that would produce different output:

1
ssh -i /root/.ssh/id_fanctl root@192.168.172.10 id

If that prints a temperature instead of user info, the restriction is working.

Reading temperatures: SAS is not SATA

If your drives are behind an HBA presenting them as SAS devices, a lot of common advice doesn’t apply. There are no /dev/disk/by-id/ata-* symlinks. There’s no Temperature_Celsius attribute in the SMART table. The temperature comes back as:

1
Current Drive Temperature:     43 C

I lost a while to a script that globbed ata-*, matched nothing, and reported a max of 0 — which my fan logic read as “all drives are spun down” and dutifully set the fans to minimum. Silent, wrong, and exactly the failure mode you don’t want. Use wwn-* identifiers, which cover both SAS and SATA, and treat “no readable drives” as an error rather than an idle state.

The two-enclosure problem

With a JBOD attached, smartctl in the VM sees all 15 drives identically. But the mid-wall fans in the main chassis do nothing for the 7 drives in the other box. If a JBOD drive ends up as your maximum, the script will chase a temperature it cannot affect and sit at 100% forever.

Sort them out with SES data:

1
2
3
4
5
6
7
8
apt install -y sg3-utils lsscsi
for e in /sys/class/enclosure/*; do
  echo "=== $e"
  cat "$e"/device/vendor "$e"/device/model 2>/dev/null
  for s in "$e"/*/device/block/*; do
    [[ -e $s ]] && echo "  $(basename $s)"
  done
done

Mine came back as two LSI SAS3x28 expanders, one with 8 drives and one with 7 — matching the physical split. But drive count is circumstantial. Confirm which enclosure is which by lighting a locate LED and walking over to look:

1
2
sg_ses --index=0 --set=locate /dev/sg12
sg_ses --index=0 --clear=locate /dev/sg12

Then whitelist the local drives by WWN. I keep them in a file rather than deriving the split at runtime, because enclosure paths can shift if you re-cable, and a silent misclassification here means a cage full of drives cooling on assumptions.

/root/scripts/local-wwns on the VM:

1
2
3
4
5
6
7
8
9
10
# Enclosure 1:0:8:0 (LSI SAS3x28) — main chassis, IPMI-cooled.
# JBOD drives (enclosure 8:0:7:0) deliberately excluded.
wwn-0x5000c500a74282db   # sdb  IBM ST14000NM0288
wwn-0x5000cca264c4eb64   # sdc  WDC W7214A520ORA014T
wwn-0x5000cca267f7d600   # sdd  WD100EMAZ
wwn-0x5000c500a7a0456f   # sde  IBM ST14000NM0288
wwn-0x5000cca2b00e4870   # sdf  HGST HUH721212AL4201
wwn-0x5000c500c79306da   # sdg  ST8000VN004
wwn-0x5000c500ada6b183   # sdh  IBM ST14000NM0288
wwn-0x5000c500a7a06ee3   # sdi  IBM ST14000NM0288

The temperature reader

/root/scripts/disktemps on the VM:

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
#!/usr/bin/env bash
# Max temperature across drives in the IPMI-controlled chassis only.
# stdout: single integer (C). Non-zero exit = caller must fail safe.
set -uo pipefail

WWNS=/root/scripts/local-wwns
max=0
found=0

[[ -r $WWNS ]] || { echo "ERR_NO_WWN_LIST" >&2; exit 2; }

while read -r w _; do
  [[ -z $w || $w == \#* ]] && continue
  d="/dev/disk/by-id/$w"
  [[ -b $d ]] || { echo "ERR_MISSING:$w" >&2; exit 2; }
  found=$((found+1))
  t=$(smartctl -A -n standby "$d" 2>/dev/null \
      | awk '/Current Drive Temperature/{print $4}
             /Temperature_Celsius/{print $10}
             /^Current Temperature:/{print $3}' | head -1)
  [[ -n ${t:-} && $t =~ ^[0-9]+$ ]] && (( t > max )) && max=$t
done < "$WWNS"

(( found == 0 )) && { echo "ERR_NO_DEVICES" >&2; exit 2; }
(( max == 0 ))   && { echo "ERR_NO_TEMPS" >&2; exit 2; }
echo "$max"

Every failure path exits non-zero. A missing drive, an empty whitelist, an unreadable temperature — all of them are faults, not quiet zeros. The caller turns any of them into maximum fan speed.

The controller

/root/scripts/fanctl.sh on the Proxmox host:

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
#!/usr/bin/env bash
# Drive-temp-driven IPMI fan control for the local 826 chassis.
# Fails loud: any error pins fans at 100%.
set -uo pipefail

VM=192.168.172.10
KEY=/root/.ssh/id_fanctl
STATE=/run/fanctl.duty
LOG=/var/log/fanctl.log
HC_URL="https://healthchecks.example.com/ping/YOUR-UUID-HERE"

FLOOR=20           # measured: below ~0x14 the BMC clamps and stops tracking
STEP=8             # max ramp-down per run; ramp-up is immediate

set_duty() { ipmitool raw 0x30 0x70 0x66 0x01 0x00 "$(printf '0x%02x' "$1")" >/dev/null 2>&1; }

panic() {
  set_duty 100
  echo 100 > "$STATE"
  echo "$(date -Is) FAIL: $* — fans forced to 100%" | tee -a "$LOG" >&2
  [[ -n $HC_URL ]] && curl -fsS -m 10 "${HC_URL}/fail" -d "$*" >/dev/null 2>&1
  exit 1
}

# Ensure Full (manual) mode — a BMC reset silently reverts this to Optimal,
# after which duty writes are accepted but immediately overridden.
mode=$(ipmitool raw 0x30 0x45 0x00 2>/dev/null | tr -d ' ')
[[ $mode == 01 ]] || ipmitool raw 0x30 0x45 0x01 0x01 >/dev/null 2>&1

max=$(timeout 30 ssh -i "$KEY" -o BatchMode=yes -o ConnectTimeout=10 \
        root@"$VM" true 2>/dev/null) || panic "ssh to $VM failed"
[[ $max =~ ^[0-9]+$ ]] || panic "bad temp value: ${max:-empty}"
(( max < 10 || max > 90 )) && panic "implausible temp: $max"

if   (( max >= 44 )); then duty=100
elif (( max >= 41 )); then duty=78
elif (( max >= 40 )); then duty=58
elif (( max >= 38 )); then duty=38
else                       duty=$FLOOR
fi

prev=$(cat "$STATE" 2>/dev/null || echo 100)
[[ $prev =~ ^[0-9]+$ ]] || prev=100

# Ramp down gradually, up immediately. The gaps between bands provide the
# hysteresis; no additional deadband is needed.
(( duty < prev - STEP )) && duty=$(( prev - STEP ))
(( duty < FLOOR )) && duty=$FLOOR

set_duty "$duty" || panic "ipmitool set_duty $duty failed"
echo "$duty" > "$STATE"

# Fan health: flag if one fan is significantly slower than its siblings.
# The BMC's own thresholds won't catch a fan running at half speed.
sleep 5
rpms=$(ipmitool sensor list 2>/dev/null | awk '/^FAN[234]/{print $3}' | cut -d. -f1)
hi=$(echo "$rpms" | sort -n | tail -1)
lo=$(echo "$rpms" | sort -n | head -1)
if [[ -n ${hi:-} && -n ${lo:-} ]] && (( hi > 0 && (hi - lo) * 100 / hi > 25 )); then
  echo "$(date -Is) WARN: fan spread ${lo}-${hi} RPM" | tee -a "$LOG" >&2
fi

echo "$(date -Is) max=${max}C duty=${duty}%" | tee -a "$LOG"
[[ -n $HC_URL ]] && curl -fsS -m 10 "$HC_URL" >/dev/null 2>&1
exit 0

A few decisions worth explaining.

Ramp-up is immediate; ramp-down is capped at 8 points per run. Spinning hard drive temperatures have a long cool down after a load finishes, and dropping straight to the floor puts you right back into a ramp. With a 2-minute timer, walking from 100% to 20% takes about 20 minutes.

The mode is restarted every run. A BMC reset or firmware event drops you back to Optimal, and without this check your duty writes would be silently overridden while the script cheerfully logged success.

systemd

1
2
3
4
5
6
7
8
9
10
# /etc/systemd/system/fanctl.service
[Unit]
Description=IPMI drive-temp fan control
After=network-online.target
Wants=network-online.target

[Service]
Type=oneshot
ExecStart=/root/scripts/fanctl.sh
SyslogIdentifier=fanctl
1
2
3
4
5
6
7
8
9
10
11
# /etc/systemd/system/fanctl.timer
[Unit]
Description=Run IPMI fan control every 2 minutes

[Timer]
OnBootSec=3min
OnUnitActiveSec=2min
AccuracySec=10s

[Install]
WantedBy=timers.target

And a unit that hands control back to the BMC when the host shuts down, so a powered-but-idle machine never sits at 20% with nothing managing it:

1
2
3
4
5
6
7
8
9
10
11
12
13
14
# /etc/systemd/system/fanctl-restore.service
[Unit]
Description=Restore BMC fan control on shutdown
DefaultDependencies=no
Before=shutdown.target

[Service]
Type=oneshot
RemainAfterExit=yes
ExecStart=/bin/true
ExecStop=/usr/bin/ipmitool raw 0x30 0x45 0x01 0x04

[Install]
WantedBy=multi-user.target
1
2
3
systemctl daemon-reload
systemctl enable --now fanctl-restore.service
systemctl enable --now fanctl.timer

0x04 is Heavy IO, which runs the peripheral zone at full and leaves the CPU zone to the BMC. It’s the right unattended default. Note that this unit must stay active for its entire life — stopping it is what triggers the restore.

Log to a file, not the journal

I wrote this to logger initially and spent an embarrassing amount of time wondering why nothing appeared. Two separate causes: logger failing silently under set -uo pipefail without -e, and a journald SystemMaxUse=64M cap that had been full for a while, the host had been quietly losing all journal history, not just mine. So… I’m compounding my errors now ;)

A plain file is better for this anyway. When you’re tuning, you want a clean timestamped series you can tail -f, not something interleaved with everything else a Proxmox host says.

1
2
3
4
5
6
7
/var/log/fanctl.log {
    weekly
    rotate 4
    compress
    missingok
    notifempty
}

Verify it fails loud

This is the step that separates a fan controller from a liability. It’s worth investigating that that if the host goes away, things don’t overheat. Noise is better than dead hardware. Suspend the VM and confirm the fans actually ramp up:

1
2
3
4
qm suspend <VMID>
# wait ~2 minutes — fans should audibly ramp, log should show FAIL,
# and your monitoring should alert
qm resume <VMID>

Check that the alert reaches you, not just that the ping fires. The entire safety argument for taking manual control of your cooling rests on this thing working.

What the numbers actually looked like

After tuning, at idle:

1
2
3
2026-08-13T09:22:22-04:00 max=36C duty=20%
2026-08-13T09:24:32-04:00 max=36C duty=20%
2026-08-13T09:26:43-04:00 max=36C duty=20%

Flat at the floor, ~2660 RPM, drives at 35–37 °C.

Under a load like a SnapRAID sync from 02:03 to 02:39 running straight into a scrub from 02:39 to 04:14, 130 minutes continuous, the peak was 36 °C and duty never exceeded 38%. My bands above 38 °C have never fired. I’ve left them in as insurance, but I’m not going to pretend they’re tuned, because they’ve never been exercised.

Your numbers will differ based on drive count, drive models, cage design, and room ambient. Mine are from mid-August; January will read lower and next summer may push into bands that have never fired. Who knows?!

The part that actually mattered

Partway through tuning, I opened the case and found one of the three mid-wall fans wasn’t seated properly.

Reseating it changed everything. Idle went from 40 °C at 38% duty to 32 °C at 70%, and the 20% floor, which had been thermally useless, suddenly held the mid-30s comfortably. Every measurement I’d taken before that point was of a chassis running on two-thirds of its airflow, and I’d been building a fan curve to compensate for it.

Nothing in my monitoring would have caught it other than Scrutiny saying that a drive temp had gotten over 42 °C. Uptime Kuma doesn’t watch fan RPM. SMART monitoring watches drives, not chassis fans. And the BMC’s own lower-critical threshold is 420 RPM, so a fan spinning at half speed reads as perfectly healthy. That’s why the script now logs a warning when the spread between fans exceeds 25%.

The long and the short is that I didn’t really need this tuning. I just needed to hook up the missing fan. But, I like that this will now cover proactively for failures or temp spikes in the future, so this should never happen again… hopefully.

This post is licensed under CC BY 4.0 by the author.